Sauna electrical requirements: amps, breaker and wire by heater size
Most traditional sauna heaters (4.5–9 kW) need a dedicated 240 V circuit: a 6 kW heater draws 25 A, so it needs at least a 31.3 A breaker, which means a 35 A double-pole breaker and 8 AWG copper by our estimate. Infrared saunas up to about 1.9 kW can run on a 120 V, 20 A circuit.
Quick table
| Heater | 240 V | 208 V | 120 V |
|---|---|---|---|
| 1.5 kW | 6.3 A → 15 A · 14 AWG | 7.2 A → 15 A · 14 AWG | 12.5 A → 20 A · 12 AWG |
| 2 kW | 8.3 A → 15 A · 14 AWG | 9.6 A → 15 A · 14 AWG | 16.7 A → 25 A · 10 AWG |
| 2.4 kW | 10 A → 15 A · 14 AWG | 11.5 A → 15 A · 14 AWG | 20 A → 25 A · 10 AWG |
| 3 kW | 12.5 A → 20 A · 12 AWG | 14.4 A → 20 A · 12 AWG | not used |
| 4.5 kW | 18.8 A → 25 A · 10 AWG | 21.6 A → 30 A · 10 AWG | not used |
| 6 kW | 25 A → 35 A · 8 AWG | 28.8 A → 40 A · 8 AWG | not used |
| 8 kW | 33.3 A → 45 A · 6 AWG | 38.5 A → 50 A · 6 AWG | not used |
| 9 kW | 37.5 A → 50 A · 6 AWG | 43.3 A → 60 A · 4 AWG | not used |
| 10.5 kW | 43.8 A → 60 A · 4 AWG | 50.5 A → 70 A · 4 AWG | not used |
| 12 kW | 50 A → 70 A · 4 AWG | 57.7 A → 80 A · 3 AWG | not used |
Why 125%?
A sauna heater can run for hours, so the electrical code treats it as a continuous load: the circuit has to be rated for at least 125% of the heater's running current. Breakers come in standard sizes (15, 20, 25, 30, 35, 40, 45, 50, 60 A…), so the result rounds up to the next size.
Makers sometimes specify a smaller breaker than this rule gives (for example, several list a 30 A circuit for their 6 kW barrels). When the heater or sauna maker states a circuit, follow the maker's manual; every model page shows the maker's figure when it's published.
208 V buildings
Some condos and commercial buildings supply 208 V instead of 240 V. A heater rated for 240 V puts out about 25% less heat at 208 V (power scales with voltage squared), so pick a heater rated for 208 V or size up.
What the makers say
Running current published by the heater makers in our data:
- Harvia KIP60B 6 kW 240VAC Steel UL (JC60B2401) 6 kW · 240 V · 25 A source
- Harvia KIP80B 8 kW 240VAC 1ph (JH80B2401) 8 kW · 240 V · 33.4 A source
- Saunum Air 5 4.8 kW · 240 V · 20 A source
- Saunum Air 7 6.4 kW · 240 V · 26.67 A source
- Saunum Air 10 9.6 kW · 240 V · 40.83 A source
Before you call an electrician
- Check your panel has two free slots for a double-pole breaker and spare capacity (a load calculation).
- Measure the run from the panel to the sauna; long runs to an outdoor sauna may need a larger wire or a subpanel.
- Many heaters need a separate control circuit or a specific wire type; read the installation manual first.
- Outdoor runs need wet-rated wire in conduit or direct-burial cable, plus a disconnect within sight of the sauna in many areas.